Appendix F: Terminal Control Diagrams
Wall Control Connection
Three types of remote wall controls are available:
1. Standard wall control with fan switch and dehumidi-
stat control.
2. Xtra wall control with fan mode selection, dehumidi-
stat control and maintenance indicator.
3. Aqua Air wall control with fan mode selection, dehu-
midistat control and high speed recirculation mode.
The remote wall controls work with the integrated elec-
tronic controls within the unit to control ventilation
sequences. Each wall control has different features and
requires four-wire connection to the unit as shown below.
Without the wall control, fans can be operated with a re-
mote fan switch as shown in Remote Fan Control.
Occupied Timer/Sensor Connection
Occupancy control is achieved by connection to the termi-
nal interface shown below. These terminals require a dry
contact which could be provided by a number of types of
controls such as a timer, light sensor, occupancy sensor,
Building Management System or other. The unit will not
operate unless these contacts are closed!
The illustration below shows a factory installed jumper and
programmable timer option.
IMPORTANT
All controls accessories (ex. night setback timer, CO
2
con-
troller, enthalpy controller or smoke detector) intended
to provide a contact closure for occupancy control across
terminals 3 and 4 (left side) cannot be used in conjunc-
tion with the Xtra or Aqua Air wall controls.
If a wall control is required in addition to any of these
options, only the standard wall control may be used.
Without these options, a factory installed jumper across
terminals 3 and 4 (left side) must be installed.
IMPORTANT
All controls accessories (ex. night setback timer, CO
2
con-
troller, enthalpy controller or smoke detector) intended
to provide a contact closure for occupancy control across
terminals 3 and 4 (left side) cannot be used in conjunc-
tion with the Xtra or Aqua Air wall controls.
If a wall control is required in addition to any of these
options, only the standard wall control may be used.
Without these options, a factory installed jumper across
terminals 3 and 4 (left side) must be installed.
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
WALL CONTROL
CLASS 2 VOLTAGE
BLACK
OCCUPIED
TIMER/
SENSOR
FAN
INTERLOCK
CONTACT
LOW
COMMON
HIGH
RED
GREEN
YELLOW
NOTE:
Connections are all dry
contacts except wall control
and 24 VAC power supply.
Use of 24 VAC circuit
requires isolating contacts
(ex. thermostat) to prevent
interconnection of Class 2
outputs.
WALL
CONTROL
JUMPER
Figure F1: Wall control connection
NOTE:
Connections are all dry
contacts except wall control
and 24 VAC power supply.
Use of 24 VAC circuit
requires isolating contacts
(ex. thermostat) to prevent
interconnection of Class 2
outputs.
WALL CONTROL
CLASS 2 VOLTAGE
BLACK
OCCUPIED
TIMER/
SENSOR
24 (−) VAC
24 (+) VAC
FAN
INTERLOCK
CONTACT
LOW
COMMON
HIGH
RED
GREEN
YELLOW
JUMPER
(factory installed)
OCC. CONTROL
(field installed)
NSB Timer
JUMPER
WALL CONTROL
CLASS 2 VOLTAGE
BLACK
OCCUPIED
TIMER/
SENSOR
FAN
INTERLOCK
CONTACT
LOW
COMMON
HIGH
RED
GREEN
YELLOW
NOTE:
Connections are all dry
contacts except wall control
and 24 VAC power supply.
Use of 24 VAC circuit
requires isolating contacts
(ex. thermostat) to prevent
interconnection of Class 2
outputs.
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
12345
M
Figure F2: Occupied timer/sensor connection
VCES-HRV-IOM-1C – HRV600i, HRV700i, HRV1200i
26